- SDV5-280EAM
- SDV5-335EAM
- SDV5-400EAM
- SDV5-450EAM
- SDV5-500EAM
- SDV5-560EAM
- SDV5-615EAM
- SDV5-670EAM
- SDV5-785EAM
- SDV5-850EAM
- SDV5-900EAM
Horse Power | HP | 10 | – |
Power Supply | – | 380–415 / 3 / 50 | V / Ph / Hz |
Capacity | Cooling | 28,0 | kW |
Power Input | Cooling | 6,3 | kW |
EER | – | 4,50 | kW / kW |
Capacity | Heating | 28,0 | kW |
Power Input | Heating | 5,2 | kW |
COP | – | 5,40 | kW / kW |
Combination of Indoor Units | – | 50–130 % of Outdoor Unit Capacity | – |
Number of indoor units | – | 16 | pcs |
Refrigerant / Charge / Eq. CO2 | – | R410A / 11,0 / 23,0 | type / kg / t |
Compressor | Type | DC Inverter EVI | – |
Compressor | Quantity | 1 | – |
Compressor | Oil | FV68H | – |
Operating Range – Cooling | – | – 5 ~ 48 | °C |
Operating Range – Heating | – | – 25 ~ 24 | °C |
Sound Pressure Level at 1 m | – | 58 | dB(A) |
Sound power level | – | 78 | dB(A) |
Airflow | – | 11000 | m3 / h |
Net Weight | – | 227,0 | kg |
Gross Weight | – | 242,0 | kg |
Net Dimension | w x h x d | 990 x 1635 x 790 | mm |
Packing Dimensions | w x h x d | 1090 x 1805 x 860 | mm |
Package volume | – | 1,692 | m3 |
Pipe Diameter | Liquid Side | 12,7 | mm |
Pipe Diameter | Gas Side | 25,4 | mm |
Horse Power | HP | 12 | – |
Power Supply | – | 380–415 / 3 / 50 | V / Ph / Hz |
Capacity | Cooling | 33,5 | kW |
Power Input | Cooling | 8,7 | kW |
EER | – | 3,90 | kW / kW |
Capacity | Heating | 33,5 | kW |
Power Input | Heating | 6,6 | kW |
COP | – | 5,10 | kW / kW |
Combination of Indoor Units | – | 50–130 % of Outdoor Unit Capacity | – |
Number of indoor units | – | 20 | pcs |
Refrigerant / Charge / Eq. CO2 | – | R410A / 11,0 / 23,0 | type / kg / t |
Compressor | Type | DC Inverter EVI | – |
Compressor | Quantity | 1 | – |
Compressor | Oil | FV68H | – |
Operating Range – Cooling | – | – 5 ~ 48 | °C |
Operating Range – Heating | – | – 25 ~ 24 | °C |
Sound Pressure Level at 1 m | – | 60 | dB(A) |
Sound power level | – | 81 | dB(A) |
Airflow | – | 11000 | m3 / h |
Net Weight | – | 227,0 | kg |
Gross Weight | – | 242,0 | kg |
Net Dimension | w x h x d | 990 x 1635 x 790 | mm |
Packing Dimensions | w x h x d | 1090 x 1805 x 860 | mm |
Package volume | – | 1,692 | m3 |
Pipe Diameter | Liquid Side | 15,9 | mm |
Pipe Diameter | Gas Side | 28,6 | mm |
Horse Power | HP | 14 | – |
Power Supply | – | 380–415 / 3 / 50 | V / Ph / Hz |
Capacity | Cooling | 40,0 | kW |
Power Input | Cooling | 9,9 | kW |
EER | – | 4,10 | kW / kW |
Capacity | Heating | 40,0 | kW |
Power Input | Heating | 8,5 | kW |
COP | – | 4,70 | kW / kW |
Combination of Indoor Units | – | 50–130 % of Outdoor Unit Capacity | – |
Number of indoor units | – | 23 | pcs |
Refrigerant / Charge / Eq. CO2 | – | R410A / 13,0 / 27,1 | type / kg / t |
Compressor | Type | DC Inverter EVI | – |
Compressor | Quantity | 1 | – |
Compressor | Oil | FV68H | – |
Operating Range – Cooling | – | – 5 ~ 48 | °C |
Operating Range – Heating | – | – 25 ~ 24 | °C |
Sound Pressure Level at 1 m | – | 62 | dB(A) |
Sound power level | – | 85 | dB(A) |
Airflow | – | 13000 | m3 / h |
Net Weight | – | 277,0 | kg |
Gross Weight | – | 304,0 | kg |
Net Dimension | w x h x d | 1340 x 1635 x 850 | mm |
Packing Dimensions | w x h x d | 1405 x 1805 x 910 | mm |
Package volume | – | 2,308 | m3 |
Pipe Diameter | Liquid Side | 15,9 | mm |
Pipe Diameter | Gas Side | 31,8 | mm |
Horse Power | HP | 16 | – |
Power Supply | – | 380–415 / 3 / 50 | V / Ph / Hz |
Capacity | Cooling | 45,0 | kW |
Power Input | Cooling | 12,0 | kW |
EER | – | 3,80 | kW / kW |
Capacity | Heating | 45,0 | kW |
Power Input | Heating | 9,8 | kW |
COP | – | 4,60 | kW / kW |
Combination of Indoor Units | – | 50–130 % of Outdoor Unit Capacity | – |
Number of indoor units | – | 26 | pcs |
Refrigerant / Charge / Eq. CO2 | – | R410A / 13,0 / 27,1 | type / kg / t |
Compressor | Type | DC Inverter EVI | – |
Compressor | Quantity | 1 | – |
Compressor | Oil | FV68H | – |
Operating Range – Cooling | – | – 5 ~ 48 | °C |
Operating Range – Heating | – | – 25 ~ 24 | °C |
Sound Pressure Level at 1 m | – | 65 | dB(A) |
Sound power level | – | 88 | dB(A) |
Airflow | – | 13000 | m3 / h |
Net Weight | – | 277,0 | kg |
Gross Weight | – | 304,0 | kg |
Net Dimension | w x h x d | 1340 x 1635 x 850 | mm |
Packing Dimensions | w x h x d | 1405 x 1805 x 910 | mm |
Package volume | – | 2,308 | m3 |
Pipe Diameter | Liquid Side | 15,9 | mm |
Pipe Diameter | Gas Side | 31,8 | mm |
Horse Power | HP | 18 | – |
Power Supply | – | 380–415 / 3 / 50 | V / Ph / Hz |
Capacity | Cooling | 50,0 | kW |
Power Input | Cooling | 12,5 | kW |
EER | – | 4,00 | kW / kW |
Capacity | Heating | 50,0 | kW |
Power Input | Heating | 10,6 | kW |
COP | – | 4,70 | kW / kW |
Combination of Indoor Units | – | 50–130 % of Outdoor Unit Capacity | – |
Number of indoor units | – | 29 | pcs |
Refrigerant / Charge / Eq. CO2 | – | R410A / 17,0 / 35,5 | type / kg / t |
Compressor | Type | DC Inverter EVI | – |
Compressor | Quantity | 2 | – |
Compressor | Oil | FV68H | – |
Operating Range – Cooling | – | – 5 ~ 48 | °C |
Operating Range – Heating | – | – 25 ~ 24 | °C |
Sound Pressure Level at 1 m | – | 65 | dB(A) |
Sound power level | – | 88 | dB(A) |
Airflow | – | 17000 | m3 / h |
Net Weight | – | 295,0 | kg |
Gross Weight | – | 322,0 | kg |
Net Dimension | w x h x d | 1340 x 1635 x 850 | mm |
Packing Dimensions | w x h x d | 1405 x 1805 x 910 | mm |
Package volume | – | 2,308 | m3 |
Pipe Diameter | Liquid Side | 19,1 | mm |
Pipe Diameter | Gas Side | 31,8 | mm |
Horse Power | HP | 20 | – |
Power Supply | – | 380–415 / 3 / 50 | V / Ph / Hz |
Capacity | Cooling | 56,0 | kW |
Power Input | Cooling | 15,1 | kW |
EER | – | 3,70 | kW / kW |
Capacity | Heating | 56,0 | kW |
Power Input | Heating | 12,7 | kW |
COP | – | 4,40 | kW / kW |
Combination of Indoor Units | – | 50–130 % of Outdoor Unit Capacity | – |
Number of indoor units | – | 33 | pcs |
Refrigerant / Charge / Eq. CO2 | – | R410A / 17,0 / 35,5 | type / kg / t |
Compressor | Type | DC Inverter EVI | – |
Compressor | Quantity | 2 | – |
Compressor | Oil | FV68H | – |
Operating Range – Cooling | – | – 5 ~ 48 | °C |
Operating Range – Heating | – | – 25 ~ 24 | °C |
Sound Pressure Level at 1 m | – | 66 | dB(A) |
Sound power level | – | 88 | dB(A) |
Airflow | – | 17000 | m3 / h |
Net Weight | – | 344,0 | kg |
Gross Weight | – | 364,0 | kg |
Net Dimension | w x h x d | 1340 x 1635 x 825 | mm |
Packing Dimensions | w x h x d | 1405 x 1805 x 910 | mm |
Package volume | – | 2,308 | m3 |
Pipe Diameter | Liquid Side | 19,1 | mm |
Pipe Diameter | Gas Side | 31,8 | mm |
Horse Power | HP | 22 | – |
Power Supply | – | 380–415 / 3 / 50 | V / Ph / Hz |
Capacity | Cooling | 61,5 | kW |
Power Input | Cooling | 18,4 | kW |
EER | – | 3,70 | kW / kW |
Capacity | Heating | 61,5 | kW |
Power Input | Heating | 15,0 | kW |
COP | – | 4,10 | kW / kW |
Combination of Indoor Units | – | 50–130 % of Outdoor Unit Capacity | – |
Number of indoor units | – | 36 | pcs |
Refrigerant / Charge / Eq. CO2 | – | R410A / 17,0 / 35,5 | type / kg / t |
Compressor | Type | DC Inverter EVI | – |
Compressor | Quantity | 2 | – |
Compressor | Oil | FV68H | – |
Operating Range – Cooling | – | – 5 ~ 48 | °C |
Operating Range – Heating | – | – 25 ~ 24 | °C |
Sound Pressure Level at 1 m | – | 66 | dB(A) |
Sound power level | – | 88 | dB(A) |
Airflow | – | 17000 | m3 / h |
Net Weight | – | 344,0 | kg |
Gross Weight | – | 364,0 | kg |
Net Dimension | w x h x d | 1340 x 1635 x 825 | mm |
Packing Dimensions | w x h x d | 1405 x 1805 x 910 | mm |
Package volume | – | 2,308 | m3 |
Pipe Diameter | Liquid Side | 19,1 | mm |
Pipe Diameter | Gas Side | 31,8 | mm |
Horse Power | HP | 24 | – |
Power Supply | – | 380–415 / 3 / 50 | V / Ph / Hz |
Capacity | Cooling | 67,0 | kW |
Power Input | Cooling | 18,1 | kW |
EER | – | 3,70 | kW / kW |
Capacity | Heating | 67,0 | kW |
Power Input | Heating | 14,9 | kW |
COP | – | 4,50 | kW / kW |
Combination of Indoor Units | – | 50–130 % of Outdoor Unit Capacity | – |
Number of indoor units | – | 39 | pcs |
Refrigerant / Charge / Eq. CO2 | – | R410A / 22,0 / 45,9 | type / kg / t |
Compressor | Type | DC Inverter EVI | – |
Compressor | Quantity | 2 | – |
Compressor | Oil | FV68H | – |
Operating Range – Cooling | – | – 5 ~ 48 | °C |
Operating Range – Heating | – | – 25 ~ 24 | °C |
Sound Pressure Level at 1 m | – | 67 | dB(A) |
Sound power level | – | 89 | dB(A) |
Airflow | – | 25000 | m3 / h |
Net Weight | – | 407,0 | kg |
Gross Weight | – | 430,0 | kg |
Net Dimension | w x h x d | 1730 x 1830 x 850 | mm |
Packing Dimensions | w x h x d | 1800 x 2000 x 910 | mm |
Package volume | – | 3,276 | m3 |
Pipe Diameter | Liquid Side | 19,1 | mm |
Pipe Diameter | Gas Side | 31,8 | mm |
Horse Power | HP | 28 | – |
Power Supply | – | 380–415 / 3 / 50 | V / Ph / Hz |
Capacity | Cooling | 78,5 | kW |
Power Input | Cooling | 24,2 | kW |
EER | – | 3,30 | kW / kW |
Capacity | Heating | 78,5 | kW |
Power Input | Heating | 20,7 | kW |
COP | – | 3,80 | kW / kW |
Combination of Indoor Units | – | 50–130 % of Outdoor Unit Capacity | – |
Number of indoor units | – | 46 | pcs |
Refrigerant / Charge / Eq. CO2 | – | R410A / 22,0 / 45,9 | type / kg / t |
Compressor | Type | DC Inverter EVI | – |
Compressor | Quantity | 2 | – |
Compressor | Oil | FV68H | – |
Operating Range – Cooling | – | – 5 ~ 48 | °C |
Operating Range – Heating | – | – 25 ~ 24 | °C |
Sound Pressure Level at 1 m | – | 68 | dB(A) |
Sound power level | – | 90 | dB(A) |
Airflow | – | 25000 | m3 / h |
Net Weight | – | 429,0 | kg |
Gross Weight | – | 452,0 | kg |
Net Dimension | w x h x d | 1730 x 1830 x 850 | mm |
Packing Dimensions | w x h x d | 1800 x 2000 x 910 | mm |
Package volume | – | 3,276 | m3 |
Pipe Diameter | Liquid Side | 22,2 | mm |
Pipe Diameter | Gas Side | 31,8 | mm |
Horse Power | HP | 30 | – |
Power Supply | – | 380–415 / 3 / 50 | V / Ph / Hz |
Capacity | Cooling | 85,0 | kW |
Power Input | Cooling | 27,4 | kW |
EER | – | 3,10 | kW / kW |
Capacity | Heating | 85,0 | kW |
Power Input | Heating | 23,0 | kW |
COP | – | 3,70 | kW / kW |
Combination of Indoor Units | – | 50–130 % of Outdoor Unit Capacity | – |
Number of indoor units | – | 50 | pcs |
Refrigerant / Charge / Eq. CO2 | – | R410A / 25,0 / 55,2 | type / kg / t |
Compressor | Type | DC Inverter EVI | – |
Compressor | Quantity | 2 | – |
Compressor | Oil | FV68H | – |
Operating Range – Cooling | – | – 5 ~ 48 | °C |
Operating Range – Heating | – | – 25 ~ 24 | °C |
Sound Pressure Level at 1 m | – | 68 | dB(A) |
Sound power level | – | 90 | dB(A) |
Airflow | – | 24000 | m3 / h |
Net Weight | – | 429,0 | kg |
Gross Weight | – | 452,0 | kg |
Net Dimension | w x h x d | 1730 x 1830 x 850 | mm |
Packing Dimensions | w x h x d | 1800 x 2000 x 910 | mm |
Package volume | – | 3,276 | m3 |
Pipe Diameter | Liquid Side | 22,2 | mm |
Pipe Diameter | Gas Side | 31,8 | mm |
Horse Power | HP | 32 | – |
Power Supply | – | 380–415 / 3 / 50 | V / Ph / Hz |
Capacity | Cooling | 90,0 | kW |
Power Input | Cooling | 31,0 | kW |
EER | – | 2,90 | kW / kW |
Capacity | Heating | 90,0 | kW |
Power Input | Heating | 25,7 | kW |
COP | – | 3,50 | kW / kW |
Combination of Indoor Units | – | 50–130 % of Outdoor Unit Capacity | – |
Number of indoor units | – | 53 | pcs |
Refrigerant / Charge / Eq. CO2 | – | R410A / 25,0 / 55,2 | type / kg / t |
Compressor | Type | DC Inverter EVI | – |
Compressor | Quantity | 2 | – |
Compressor | Oil | FV68H | – |
Operating Range – Cooling | – | – 5 ~ 48 | °C |
Operating Range – Heating | – | – 25 ~ 24 | °C |
Sound Pressure Level at 1 m | – | 68 | dB(A) |
Sound power level | – | 90 | dB(A) |
Airflow | – | 24000 | m3 / h |
Net Weight | – | 475,0 | kg |
Gross Weight | – | 507,0 | kg |
Net Dimension | w x h x d | 1730 x 1830 x 850 | mm |
Packing Dimensions | w x h x d | 1800 x 2000 x 910 | mm |
Package volume | – | 3,276 | m3 |
Pipe Diameter | Liquid Side | 22,2 | mm |
Pipe Diameter | Gas Side | 38,1 | mm |